The MiifHosts worksheet contains the communication parameters for the MIIF communication driver for Simens Simotion.
This communication driver enables communication via Ethernet TCP/IP to Simotion devices. On the Simotion device TP OAMIIF must be installed!
#Hostname
|
IP address
|
Delay[ms]
|
Timeout [s]
|
Retry
|
DelayOnError [s]
|
LogLevel
|
|
|
|
|
|
Symbol file
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Driver DLL: drvMiif.dll
Communication with S7 PLCs via CP or S7-1200 series
Parameters
|
M/O
|
Default
|
Description
|
Hostname
|
M
|
|
Unique name
|
IP address
|
M
|
|
IP address of the Simotion device
|
Delay[ms]
|
O
|
200
|
Delay between two read operations (cycle time of communication task)
|
Timeout[s]
|
O
|
3
|
Maximum time that must not be exceeded when accessing the PLC. (Connect, Read, Write)
|
Retry
|
O
|
3
|
Number of retries up to error
|
DelayOnError[s]
|
O
|
3
|
Delay after an error has occurred. Prevents, for example, too fast connections during an online change
|
Loglevel
|
O
|
0
|
Levels of error output. Not implemented.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Path symbol file
|
O
|
|
Path and name of the imported symbol file
|
|